B R A G A M O R O

Modular Inverter - Vega 20K

Modular Inverter - Vega 20K

Product information

  • Three phase output
  • Power range: 18kVA/18kW
  • Sine wave output voltage
  • All modules are hot-swappable
  • Auto selects operating frequency: 50 or 60Hz
  • Integrated maintenance bypass switch
  • Touch screen controller
  • CAN-bus communication for all system modules
  • Load power factor: 0.7 lag to lead
  • Communication: RS232, USB, SNMP
  • Programmable voltage free contacts
AC Input
  • Configuration: three phase R, S, T, N, PE
  • Input voltage: 400Vac, adjustable range 260–520Vac
  • Operating frequency (auto selected):
    • 50Hz, adjustable range 45–55Hz
    • 60Hz, adjustable range 55–65Hz
  • Maximum input current: 120 × 3A
DC Input
  • Input voltage: 48Vdc, adjustable range 40–60Vdc
  • Adjustable parameter setting range (48Vdc):
    • High voltage window: 55–62Vdc; automatic restart is the set value −2Vdc
    • Low voltage window: 38–49Vdc
    • Restart: 38–52Vdc (normal setting 50Vdc)
  • Maximum input current: 48Vdc system: 476A
AC Output
  • Configuration: three phase R, S, T, N, PE
  • Output voltage:
    • Inverter output: 400Vac ±2%
    • Bypass output: 400Vac, 260–520Vac
    • Frequency: adjustable range 45–55Hz or 55–65Hz
  • Frequency regulation: 50 or 60Hz ±0.03% (unsynced)
  • Capacity: 18kVA/18kW
  • Waveform: sine wave
  • Total harmonic distortion: ≤±2% (resistive load)
  • Dynamic response: <±1% (for step resistive load change of 10–100–10%)
  • Efficiency: ≥90% (86–91% depending on model rating)
  • Current sharing: ≤±5%
  • Crest factor: 3:1
  • Power factor: 0.7 lead or lag
Transfer time
  • Inverter to bypass:
    • DC voltage exceeds the setting range or overload: 0ms
    • Inverter fail/overload: typical ≤1ms
  • Bypass to inverter:
    • AC voltage exceeds the setting range: 0ms
    • Mains loss: typical ≤1ms
Audible noise
  • ≤55dB (A)
Protection
  • DC input: over/under voltage shut down and reverse polarity protection
  • Short circuit: automatic current limit; system recovers upon removal of short circuit
  • Overload: 105–125% overload for 10 minutes; 125–150% overload for 10 seconds
  • Temperature: automatic shutdown when internal temperature exceeds 90°C, restart on temperature recovery. Fan speed is load level controlled.
Communication interface
  • RS232, USB, HTTP and SNMP
Safety standard
  • IEC60950 compliant
EMC
  • CISPR22 class B compliant
Environmental
  • Operating temperature: −5 to +50 (60)°C, see temperature graph
  • Relative humidity: <90%, non-condensing
Mechanical data
  • Dimensions W × D × H (mm): 600 × 600 × 2000
  • Weight: 200kg

Do you want more information?